CCK / Splicing fittings
JY/LY splicing tube and insulation cover

CCK Power Fittings
JY/LY splicing tube and insulation cover for joining two conductor lengths.
Product details
- Product
- JY/LY splicing tube and insulation cover
- Category
- Splicing fittings
- Model references
- JY-35Y / JKLGYJ-35 / JY-35/50 / JY-50Y / JKLGYJ-50 / JY-70LY / JKLGYJ-70 / JY-70/95 / JY-95LY / JKLGYJ-95 / JY-120LY / JKLGYJ-120 / JY-120/150 / JY-150LY / JKLGYJ-150 / JY-185LY / JKLGYJ-185 / JY-185/240 / JY-240LY / JKLGYJ-240 / JY-300LY / JKLGYJ-300 / JY-300 / JY-70/10 / JY-95/15 / JY-120/20 / JY-150/25 / JY-185/25 / JY-240/30
- Materials
- Aluminium alloy / Aluminium
- Standards
- To be agreed in the project specification
Specifications and drawings
Check the model, units and dimension symbols against the drawing. Breaking loads and working loads are different values and must not be used interchangeably.
| Model | Suitable Conductor | Main Dimensions(mm) | Grip Strength (kN) | Mating insulating cover | ||
|---|---|---|---|---|---|---|
| L | D | d | ||||
| JY-35Y | JKLGYJ-35 | 7.6 | 20 | 130 | 4.9 | JY-35/50 |
| JY-50Y | JKLGYJ-50 | 9.0 | 20 | 140 | 6.7 | JY-35/50 |
| JY-70LY | JKLGYJ-70 | 11.0 | 22 | 170 | 9.8 | JY-70/95 |
| JY-95LY | JKLGYJ-95 | 12.5 | 24 | 180 | 13.0 | JY-70/95 |
| JY-120LY | JKLGYJ-120 | 14.0 | 26 | 210 | 16.5 | JY-120/150 |
| JY-150LY | JKLGYJ-150 | 15.5 | 28 | 240 | 20.0 | JY-120/150 |
| JY-185LY | JKLGYJ-185 | 17.0 | 32 | 260 | 25.4 | JY-185/240 |
| JY-240LY | JKLGYJ-240 | 19.5 | 34 | 290 | 33.0 | JY-185/240 |
| JY-300LY | JKLGYJ-300 | 22.0 | 36 | 310 | 38.7 | JY-300 |
| Model | Suitable Conductor | Main Dimensions(mm) | Grip Strength(kN) | |||||
|---|---|---|---|---|---|---|---|---|
| L | D | d | L1 | D1 | d1 | |||
| JY-70/10 | JKLGYJ70/10 | 360 | 26 | 13.0 | 110 | 12 | 4.5 | 21.0 |
| JY-95/15 | JKLGYJ95/15 | 430 | 26 | 15.0 | 130 | 14 | 5.7 | 31.5 |
| JY-120/20 | JKLGYJ120/20 | 430 | 30 | 16.0 | 130 | 14 | 6.2 | 36.9 |
| JY-150/25 | JKLGYJ150/25 | 500 | 30 | 18.5 | 150 | 14 | 7.0 | 48.7 |
| JY-185/25 | JKLGYJ185/25 | 520 | 32 | 20.5 | 150 | 14 | 7.0 | 53.5 |
| JY-240/30 | JKLGYJ240/30 | 570 | 36 | 23.0 | 170 | 16 | 7.9 | 68.0 |

CCK Power Fittings

CCK Power Fittings
Information for quotation
conductor material and cross-section, load-bearing requirements, connection method, tools and electrical performance
Contact CCK ↗Related products
Specification reference: www.yonguexport.com · Supply is subject to confirmed drawings and quotation.